Table 15-3. CS41 Four Loop Controller Datapoints
Data-
point Table Module Title and Function
De-
fault
CON3 Control Loop 4 Related Datapoints (Cont)
C223 5-9 CON3 Controller Span - Enter a value, that when added to the Loop
4 Controller Lower Range value, will produce the Loop 4
control upper range value in engineering units.
100
C224 5-9 CON3 Controller Lower Range - Enter a value that represents in
engineering units the Loop 4 control lower range value.
0
CCI0 - Remote SP Enable Loop 1
L264 5-6 CCI0 Contact Input Invert - Normally, Remote SP Enable Loop 1 is
permitted if CCI0 is closed (datapoint L115 - Remote
Setpoint Enable is set to 1 by CCI0). Set to 1 to reverse the
CCI0 condition required to permit Remote SP Enable Loop 1
(CCI0 open = Remote SP Enable Loop 1).
0
CCI1 - Remote SP Enable Loop 2
L265 5-6 CCI1 Contact Input Invert - Normally, Remote SP Enable Loop 2 is
permitted if CCI1 is closed (datapoint L139 - Remote
Setpoint Enable is set to 1 by CCI1). Set to 1 to reverse the
CCI1 condition required to permit Remote SP Enable Loop 2
(CCI1 open = Remote SP Enable Loop 2).
0
CCI2 - Remote SP Enable Loop 3
L266 5-6 CCI2 Contact Input Invert - Normally, Remote SP Enable Loop 3 is
permitted if CCI2 is closed (datapoint L163 - Remote
Setpoint Enable is set to 1 by CCI2). Set to 1 to reverse the
CCI2 condition required to permit Remote SP Enable Loop 3
(CCI2 open = Remote SP Enable Loop 3).
0
CCI3 - Remote SP Enable Loop 4
L267 5-6 CCI3 Contact Input Invert - Normally, Remote SP Enable Loop 4 is
permitted if CCI3 is closed (datapoint L187 - Remote
Setpoint Enable is set to 1 by CCI3). Set to 1 to reverse the
CCI3 condition required to permit Remote SP Enable Loop 4
(CCI3 open = Remote SP Enable Loop 4).
0
CCI4 - Force Fallback Loop 1
L268 5-6 CCI4 Contact Input Invert - Normally, Force Fallback Loop 1 is
permitted if CCI4 is open. Set to 1 to reverse the CCI4
condition required to permit Force Fallback Loop 1 (CCI4
closed = Force Fallback Loop 1).
0
C129 5-6 CON0 Output Track Value - The Control Output Loop 1 can be
forced to match the value in this datapoint if CCI4 - Force
Fallback Loop 1 is open, L119 - Output Track Enable is
configured to a 1, and Remote is selected with the R/L
faceplate push button.
0
C128 5-6 CON0 Setpoint Track Value - The Loop 1 setpoint can be forced to
match the value in this datapoint if CCI4 - Force Fallback
Loop 1 is open, L118 - Setpoint Track Enable is configured
to a 1, and Remote is selected with the R/L faceplate push
button.
0
9 of 13
Section 15. CS41 - Four Loop Controller
15-17

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ControlIT 53MC5000 and is the answer not in the manual?

ABB ControlIT 53MC5000 Specifications

General IconGeneral
BrandABB
ModelControlIT 53MC5000
CategoryController
LanguageEnglish

Related product manuals