Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 105
Table 66 Linear Outputs.
Rate Limiter
The Rate Limiter function limits the rate of change of the input Signal connected
to the block. The parameter Rate determines the limit.
If Signal has a rate of change faster then Rate then the output Va lu e is in the form
of ramp with slope Rate.
Table 67 Rate Limiter Inputs
Table 68 Rate Limiter Parameters.
Outputs
Name Type
Value Analog
Inputs
Name Connection
Signal Off, Analog
Parameters
Name Setting Unit
Rate 0.1 ≤ Rate ≤ 100.0 %/second
Available in
ECA06 ECA60 ECA600 EMA60
- XXX
Signal
Rate
Limiter
Va lu e