Chapter 5: Technical Data 5.6 Output Signals
493-0736-11 (6-2) 205
Inactive = 0 to 5 V, active = 16 to 30 V
5.6 Output Signals
AO1, AO2, AO3
Three analog outputs, 0–20 mA or 4–20 mA. Loading 0 to 650 .
Load dependence < 0.2 % for a change from 0 to 60 .
DO1, DO2, DO3, DO4, DO5, DO6
Six digital outputs, 24 V 250 mA.
5.7 Computer Communication
RS485 serial interface, COMLI or MODBUS RTU protocol.
RS232 serial interface, COMLI or MODBUS RTU protocol.
5.8 Safety Functions
Supply Failure
Restart from present position (3-state pulse output) or a preset position.
Input/Output Signal Failure
Failure of the analog input/output signal initiates an alarm.
5.9 Indications
Process and Set Point Values
Analog bar graph display with 3.33 % resolution.
Calibrated 0 to 100 %.
Display normally shows Process Value. Automatically reverts to showing the
Process Value 5 seconds after the user has finished examining other values.
Output Signal
Analog bar graph display with 5 % resolution.
Calibrated 0 to 100 %.