A.3 Furnace Pressure Control with 3-State Pulse Output Appendix A: Application Examples
230 493-0736-11 (6-2)
Configuration
When configuring the functions only those parameters with unsuitable default
values have to be changed, therefore only these points are described below.
Preset Configuration
Select the default setup from the Preset Configurations.
1System → Miscellaneous → Setup = Default.
Inputs
Configure analogue inputs AI1 to accept the potentiometer feedback signal and
AI2 to accept the pressure signal:
1 Inputs → Analog Inputs → AI1 → Mode = 0–5V.
2 Inputs → Analog Inputs → AI1 → Identity = Feedback.
3 Inputs → Analog Inputs → AI2 → Mode = 4–20mA.
Miscellaneous
SetUp
Default
Cancel
OK
AI1: Ana In 1
Mode
0–5V
Cancel
OK
AI1: Ana In 1
Identity
Feedback
Cancel
OK