3.1 Configuring the Process Value Chapter 3: Configuration
44 493-0736-11 (6-2)
Configuration Trees
The Configuration trees in Appendix C show the path to take:
Operator
Process Value
• NumberOfDecimals (0 ≤ NumberOfDecimals ≤ 4)
• MinValue (–99999 ≤ MinValue ≤ MaxValue ≤ 99999)
• MaxValue (–99999 ≤ MinValue ≤ MaxValue ≤ 99999)
•Unit (%, °C, °F, K, W, kW, MW, J, kJ, MJ, rpm, Pa, kPa, MPa, bar,
mbar, bara, l, l/s, l/min, l/h, Psi, Psig, Psia, mmWG, ”WG, mmvp,
mvp, mmH
2
O, ”H
2
O, mmHg, ”Hg, kp/cm
2
, N/m
2
, kg/cm
2
, kg/h, t/
h, Nm
3
/h, m
3
/h, t/24h, m/s, m/min, ms, ms/cm, ppm, pH, mg/l, Feet,
inches, meters, tons, lbs, lbs/sec, lbs/min, lbs/hr, ft/sec, ft/hr, BTU/
hr, BTU, ft
3
/sec, ft
3
/hr, gals, gal/sec, gal/hr, cu.ft, MPPH, cc, cm,
GPM)
Parameters to Configure
There are four parameters you can configure:
• NumberOfDecimals defines the number of decimal places displayed for the
Process Value, e.g. setting NumberOfDecimals to 3 will give a displayed
Process Value in the form 1.234.
• MinValue and MaxValue define the lower and upper limits respectively of the
acceptable range for the Process Value.
• Unit defines the engineering unit in which the Process Value is shown and
appears on the display.
Configuration Step-by-Step
The steps listed below describe how to enter the Configuration mode and set each
of these parameters in turn. As an example a Process Value within the range –20
to +120°C with two decimal places is used.
1 Press and hold the Next key.
2 If you are prompted to enter the password, press the Up and Down keys to
change the displayed number until it matches your password.
3 When the password is correct press the OK key.