A.1 Level Control with Feed Forward and Gain Scheduling Appendix A: Application Examples
214 493-0736-11 (6-2)
Configuration
Preset Configuration
Select the default setup from the Preset Configurations.
1System → Miscellaneous → Setup = Default.
Inputs
AI1 is set by default to 4–20 mA current input so there is no need to change it, but
it can be given a suitable name. However, AI2 must be configured:
1 Inputs → AI1 → Identity = Level
2 Inputs → AI2 → Mode = 0–20mA
3 Inputs → AI2 → Identity = Flow
Miscellaneous
SetUp
Default
Cancel
OK
AI1
Identity
Level
Cancel
OK
AI2
Mode
0–20 mA
Cancel
OK