Appendix A: Application Examples A.2 Temperature Control and Communication with COMLI
493-0736-11 (6-2) 223
Configuration
Preset Configuration
Select the Default Setup from the Preset Configurations.
1System → Miscellaneous → Setup = Default.
Inputs
The TT1 output signal range is 0–5V (for 0–400ºC) and the FT1 output signal
range is 0–20 mA:
1 Inputs → Analogue Inputs → AI1 → Mode = 0–5V.
2 Inputs → Analogue Inputs → AI1 → Identity = Temp.
3 Inputs → Analogue Inputs → AI2 → Mode = 0–20mA.
4 Inputs → Analogue Inputs → AI2 → Identity = Flow.
Miscellaneous
SetUp
Default
Cancel
OK
AI1: Ana In 1
Mode
0–5V
Cancel
OK
AI1: Ana In 1
Identity
Temp
Cancel
OK
AI2: Ana In 2
Mode
0–20 mA
Cancel
OK