A.2 Temperature Control and Communication with COMLI Appendix A: Application Examples
224 493-0736-11 (6-2)
Process Value
The required temperature range is 0–400ºC, with no decimal places. There is no
need to change PVMinValue as its default value is zero:
1 Operator → (PID1 – ECA600 only →) Process Value →
NumberOfDecimals = 0
2 Operator → (PID1 – ECA600 only →) Process Value →
MaxValue = 400
3 Operator → (PID1 – ECA600 only →) Process Value → Unit = ºC
AI2: Ana In 2
Identity
Flow
Cancel
OK
Process Value
NumberOfDecimals
0
Cancel
OK
Process Value
MaxValue
400
Cancel
OK
Process Value
Unit
°C
Cancel
OK