Appendix A: Communication A.1 Communication setup
493-0736-11 (6-2) 281
Appendix A
Communication
This appendix describes how to establish ECA communication with a supervisory
control system.
A.1 Communication setup
The information below facilitates the communication setup.
Serial communication interface RS485 (point to point or multidrop) or RS232
(point to point) is available. A screened twisted-pair cable is to be used. See
"Communications signal wiring, RS485", on page xxxiv.
The available protocols are COMLI and MODBUS RTU, see "COM Setup",
on page cxc.
The parity must be set to Odd (fixed) in the supervisory system.
The baud rate may be set between 1200 and 38400 baud, see "COM Setup", on
page cxc.
All ECA controllers connected to the supervisory control system (Master) are
Slaves.
Each ECA controller in a network must be set to a unique communication
identity number between #1 and #247, see "COM Setup", on page cxc.
Figure 1 ECA controllers connected in multidrop configuration to a supervisory system.
Supervisory control
system
Master
ECA Controller
Slave # 1
ECA Controller
Slave # 247
RS485