5.5 Input Signals Chapter 5: Technical Data
204 493-0736-11 (6-2)
•Integrator
Time Measurement
Rate Limiter
•Timer
Counter
Miscellaneous
Remote reading of selectable internal signals.
Password to protect configuration.
Fault Indications.
Controller and/or configuration resetting.
Alarms, fault signals and operating modes can be indicated via digital outputs.
5.5 Input Signals
AI1, AI2, AI3, AI4, AI5
Five separate analog inputs.
Fixed or floating reference ground.
Floating inputs between –5 V and +17 V relative to supply ground.
Signal ranges 0–20 mA or 4–20 mA, alternatively 0–5 V, 1–5 V,
0–10 V or 2–10 V.
Input resistance for current inputs 250 with voltage inputs >500 k.
Inaccuracy
< 0.2 % of the measuring range.
Temperature Dependency
< 0.01 % of the measuring range per °C within the range 0 to 50°C.
DI1, DI2, DI3, DI4
Four opto-isolated digital inputs for 24 V.