EasyManua.ls Logo

ABB ECA06 - Page 231

ABB ECA06
310 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A: Application Examples A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2) 231
4 Inputs → Analog Inputs → AI2 → Identity = Pressure.
Filtering
Set the time constant for AI2 to 2seconds:
1 Inputs → Analog Inputs → AI2 → FilterTime = 2 seconds.
Process Value
The pressure signal is to be used as the Process Value and is in the range –1.0 to
+1.0kPa:
1 Operator → (PID1 – ECA600 only →) Process Value →
NumberOfDecimals = 1.
2 Operator → (PID1 – ECA600 only →) Process Value →
PVMinValue = –1.
AI2: Ana In 2
Mode
4–20mA
Cancel
OK
AI2: Ana In 2
Identity
Pressure
Cancel
OK
AI2: Pressure
FilterTime
2
Cancel
OK
Process Value
NumberOfDecimals
1
Cancel
OK

Table of Contents