Appendix A: Application Examples A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2) 231
4 Inputs Analog Inputs AI2 Identity = Pressure.
Filtering
Set the time constant for AI2 to 2seconds:
1 Inputs Analog Inputs AI2 FilterTime = 2 seconds.
Process Value
The pressure signal is to be used as the Process Value and is in the range –1.0 to
+1.0kPa:
1 Operator (PID1 – ECA600 only ) Process Value
NumberOfDecimals = 1.
2 Operator (PID1 – ECA600 only ) Process Value
PVMinValue = –1.
AI2: Ana In 2
Mode
4–20mA
Cancel
OK
AI2: Ana In 2
Identity
Pressure
Cancel
OK
AI2: Pressure
FilterTime
2
Cancel
OK
Process Value
NumberOfDecimals
1
Cancel
OK