A.3 Furnace Pressure Control with 3-State Pulse Output Appendix A: Application Examples
232 493-0736-11 (6-2)
3 Operator (PID1 – ECA600 only ) Process Value
PVMaxValue = 1.
4 Operator (PID1 – ECA600 only ) Process Value Unit = kPa.
5 SetPoint Process Value PVSignal = AI2[Value].
Absolute Alarms
Set the absolute low alarm to 0.000 kPa (i.e. 0%) and the high alarm to
+0.500 kPa (i.e. 50%).
1Alarms Absolute Alarms Absolute Alarm 1 Mode = On.
Process Value
PVMinValue
–1.0
Cancel
OK
Process Value
PVMaxValue
1.0
Cancel
OK
Process Value
Unit
kPa
Cancel
OK
Process Value
PVSignal
AI2[Value]
Cancel
OK