3.6 Setting the Configuration Chapter 3: Configuration
114 493-0736-11 (6-2)
Counter
The block is used to count pulses. When the preset number of pulses on the input
CountSignal (the value in the parameter NbrOfPulses) is reached, the output
CounterDone is set to 1.
The counter is activated by the digital signal ActivateCounter and reset by the
digital signal ResetSignal or from the configuration menu.
The output CounterRunning is 1 (running) if the counter function is running and
is 0 (not running) if ActivateCounter is 0 (not active) or CounterDone is 1
(active).
CounterDone is set to 1 and CounterRunning is reset to 0 when the the preset
number of pulses is reached.
When the block is active and selected from the Operator Option List the number
of pulses counted is shown on the operators display as below.
Figure 45 Counter Display.
Available in
ECA06 ECA60 ECA600 EMA60
--XX
ActivateCounter
Counter
CountSignal
CounterRunning
CounterDone
ResetSignal
FO1: Counter 1
23427