3.6 Setting the Configuration Chapter 3: Configuration
122 493-0736-11 (6-2)
The following parameters apply to both the Simple Set Point Ramp and the
Advanced Set Point Ramp.
Table 85 Set Point Ramp Parameters.
Ramp Start Condition
The following Control Mode transitions, which represent a change from False to
True on the AutoStatus input, start the Ramp function:
•Manual Auto
Forced Output Auto
Tracking Auto
The following Control Mode transitions which represent a change from True to
False on the AutoStatus input, stop the Ramp function:
•Auto Manual
•Auto Forced Output
•Auto Tracking
Parameters
Name Setting Unit
RampMode Off, Simple, Advanced None
Hold Off, On None
TimeUnit Minutes, Seconds None
RampStart StartFromPV, StartFromStartValue None
StartValue MinValue StartValue MaxValue TimeUnit