Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 133
Disabling Selected Alarms
You may selectively disable these alarms as follows:
LoLoAlarm: Set the LoLoLimit to 0.0.
LoAlarm and LoLoAlarm: Set the LoLimit and the LoLoLimit to 0.0.
HiHiAlarm: Set the HiHiLimit to 100.0.
HiHiAlarm and HiAlarm: Set the HiLimit and the HiHiLimit to 100.0.
Table 90 Absolute Alarm Inputs
.
Table 91 Absolute Alarm Parameters.
Inputs
Name Connection
Signal Analog
Parameters
Name Setting Unit
Mode Off, On None
LoLimit 0.0 LoLoLimit LoLimit Hi Limit
HiHiLimit 100.0
%
HiLimit 0.0 LoLo Limit LoLimit HiLimit
HiHiLimit 100.0
%
LoLoLimit 0.0 LoLoLimit LoLimit HiLimit
HiHiLimit 100.0
%
HiHiLimit 0.0 LoLoLimit LoLimit HiLimit
HiHiLimit 100.0
%
Identity User defined text None