Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 135
PosAlarm = Diff > PosDeviationLimit
NegAlarm = Diff < NegDeviationLimit
Alarm = PosAlarm OR NegAlarm.
Disabling Alarms
You may selectively disable the deviation alarms as follows:
NegAlarm: Set NegDeviationLimit to –100.0.
PosAlarm: Set PosDeviationLimit to 100.0.
Table 93 Deviation Alarm Inputs.
Table 94 Deviation Alarm Parameters.
Inputs
Name Connection
Signal1 Analog
Signal2 Analog
Parameters
Name Setting Unit
Mode Off, On None
NegDeviationLimit –100.0 ≤ NegDeviationLimit ≤ 0.0 %
PosDeviationLimit 0.0 ≤ PosDeviationLimit ≤ 100.0 %
Identity User defined text None