Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 163
When Mode is set to AutoToAny it is possible for the operator to change the
control mode to Manual. If the ForcedEnable input changes from True to False
when the controller is in Manual Control mode, the Control Mode remains
unchanged.
Table 118 Manual Mode Selection.
When the controller enters Forced Output Mode, i.e. ForcedEnable is active, the
message “Forced” is shown at the left of the top line of the operator mode display.
If the operator then decides to put the controller into Manual Mode by pressing
the Hand key, the Hand key LED illuminates.
Table 119 Forced Output Parameters.
Mode Name Entry Mode Exit Mode Manual Mode
Possible
AutoToAny Auto Auto or Manual Yes
AutoToManual Auto Manual Yes
AnyToPrevious Auto or Manual Previous mode No
AnyToManual Auto or Manual Manual No
Parameters
Name Setting Unit
Mode Off, AutoToAny, AutoToManual,
AnyToManual, AnyToPrevious
n/a
ForcedValue 0.0 ForcedValue 100.0 %