Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 167
The active time of the output Pulse is proportional to the value of the input Signal.
When the input is 0%, the output signal is active for the minimum time period,
which is equal to the parameter SampleTime found in the System Block settings.
When the input signal is 100%, the output signal is equal to the parameter
CycleTime.
To connect the output pulse signal to the system under control one of the Digital
Outputs must be used.
Table 122 Two State Pulse Input.
Note: The inputs to the Output Functions block identified as fixed connections
cannot be changed. They are listed for information only.
Table 123 Two State Pulse Parameters.
Table 124 Two State Pulse Output.
For example, suppose the parameter CycleTime is set to 50 seconds. With a Signal
value of 60%, the Pulse output of the Two State Pulse block is active for 60% of
the CycleTime:
60.0% × 50 = 30
Inputs
Name Connection
Signal Fixed connection
Parameters
Name Setting Unit
CycleTime 0 CycleTime 1000 seconds
Outputs
Name Type
Pulse Digital