Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 187
Table 143 AltDisplay Parameters.
Note. The MinValue is the value shown for the internal signal value 0 and the
MaxValue is the value shown for the internal signal value 1. If the Signal into the
AltDisplay block is greater than 1 or less than 0, the value shown in the display is:
Shown Value = ((MaxValue – MinValue) x Signal + MinValue).
Unit %, °C, °F, K, W, kW, MW, J, kJ,
MJ, rpm, Pa, kPa, MPa, bar,
mbar, bara, l, l/s, l/min, l/h, Psi,
Psig, Psia, mmWG, ”WG,
mmvp, mvp, mmH
2
O, mmHg,
”Hg, kp/cm
2
, N/m
2
, kg/cm
2
, kg/
h, t/h, Nm
3
/h, m
3
/h, t/24h, m/s,
m/min, µs, µs/cm, ppm, pH, mg/
l, feet, inches, meters, tons, lbs,
lbs/sec, lbs/min, lbs/hr, ft/sec, ft/
hr, BTU/hr, BTU, ft
3
/sec, ft
3
/hr,
gals, gal/sec, gal/hr, cu.ft,
MPPH, cc, cm, GPM.
None
Tag User defined text.
Tag is a text string displayed to
the left on the top line of the unit
in Operator Mode. Tag can hold
twenty (20) characters, but the
top line cannot hold all of them.
If the length of Tag is less than or
equal to 12, the full length is
displayed. If the length of Tag is
greater than twelve (12), eleven
(11) characters are displayed
followed by the characters “…”.
None