A.1 Level Control with Feed Forward and Gain Scheduling Appendix A: Application Examples
216 493-0736-11 (6-2)
3 Operator (PID1 – ECA600 only →) Process Value Unit = mvp.
Absolute Alarms
Set the absolute low alarm to 2 mvp (i.e. 20%) and the high alarm to 8 mvp (i.e.
80%).
1Alarms Absolute Alarms Absolute Alarm 1 Mode = On.
2Alarms Absolute Alarm Absolute Alarm 1 LoLimit = 20.
3Alarms Absolute Alarm Absolute Alarm 1 HiLimit = 80.
Process Value
MaxValue
10.0
Cancel
OK
Process Value
Unit
mvp
Cancel
OK
Absolute Alarm 1
Mode
On
Cancel
OK
Absolute Alarm 1
LoLimit
20%
Cancel
OK