EasyManua.ls Logo

ABB ECA06 - Page 235

ABB ECA06
310 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A: Application Examples A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2) 235
Outputs
The feed to the potentiometer should be set to 5.0mA which gives 0–5V output
since the potentiometer resistance is 1000:
1Outputs Analog Outputs AO1 Mode = Direct.
2Outputs Analog Outputs AO1 FixedCurrent = 5 mA.
3Outputs Analog Outputs AO1 Identity = PotFeed.
Configure DO1 and DO2 to the low and high pressure alarms:
1Outputs Digital Outputs DO1 Mode = PositiveLogic.
ThreeStatePulse
Feedback
AI1[Value]
Cancel
OK
AO1: Ana Out 1
Mode
Direct
Cancel
OK
AO1: Ana Out 1
Fixed Current
5mA
Cancel
OK
AO1: Ana Out 1
Identity
PotFeed
Cancel
OK

Table of Contents

Related product manuals