Appendix A: Application Examples A.3 Furnace Pressure Control with 3-State Pulse Output
493-0736-11 (6-2) 237
Configure the controller to provide a three state pulse output from DO3 and DO4
for the motor increase/decrease signal:
1Outputs → Digital Outputs → DO3 → Mode = PositiveLogic.
2Outputs → Digital Outputs → DO3 → Signal = OF1 [Increase].
3Outputs → Digital Outputs → DO4 → Mode = PositiveLogic.
4Outputs → Digital Outputs → DO4 → Signal = OF1[Decrease].