3.6 Setting the Configuration Chapter 3: Configuration
76 493-0736-11 (6-2)
Table 19 AddSub Outputs.
Note: The AddSub block in the ECA06 does not have the input Signal3 or the
parameter Factor3 and hence the function is defined as:
Value = Factor1 × Signal1 + Factor2 × Signal2 + Bias
MulDiv
The MulDiv function has four analog inputs, Signal1, Signal2, Signal3 and
Signal4, and one analog output, Val ue . The block holds two parameters; a gain
Factor, and Bias.
Note: If any input is unconnected, it represents the value 1.0.
Outputs
Name Type
Value Analog
Available in
ECA06 ECA60 ECA600 EMA60
- XXX
Signal1
Signal2
Signal3
Signal4
MulDiv
Valu e
Value Factor
Signal1 Signal2
×
Signal3 Signal4
×
-----------------------------------------------
×
Bias+=