Chapter 3: Configuration 3.6 Setting the Configuration
493-0736-11 (6-2) 87
When Reset changes state from False to True, the output, Status, changes state to
False. The output remains False whatever happens to Reset, provided that Set does
not change.
Table 39 S/R Inputs.
Table 40 S/R Outputs.
Note: If an input is not connected it represents the value False in the calculation.
Not
Status = NOT Signal
The Not function has one digital inputs, Signal, and one digital output, Status.
The output, Status, is True whenever Signal is False, and False when Signal is
True.
Inputs
Name Connection
Set Off, Digital
Reset Off, Digital
Outputs
Name Type
Status Digital
Available in
ECA06 ECA60 ECA600 EMA60
-XXX
Signal
Not
Status