Continued from the previous page
9. Turn the crank clockwise until the pushbutton comes out and the indicator shows that
the circuit-breaker is in TEST position. See Figure 42.
Figure 42
10. Press the lock button and rotate the crank clockwise until the pushbutton comes out
and the indicator shows that the circuit-breaker is in CONNECT position. See Figure 43.
1
2
Figure 43
11. Extract the crank. See Figure 44.
12. Replace the crank in its housing See Figure 45.
Figure 44
Figure 45
To extract the moving part from the fixed part, perform the same steps indicated for insertion
in reverse order.