-EN Rev. E Operating instruction SCK Gas Sampling System 115
Proceed as follows (note: it is advisable for two people to perform this work):
Connect the filling pipe to the cooling-water supply of the
cooling module.
Note: Make sure that there are no dirt deposits in the filling
pipe; rinse first.
Note: The cooling water is tinted due to formation of metal
oxides in the heat exchanger. The functional capability is not
affected.
Note: Cooling water filling pressure > 1 bar (1000 hPa).
On the top of the heat exchanger: Unscrew cap on drain valve
and open vent cock (red).
Open drain valves
(2)
on gas sampling probe.
Slowly open the shut-off valve -J63 on the cooling module and
allow cooling water to flow in until
cooling water appears at the
drain valves of the heat exchanger and gas sampling probe.
Close shut-off valve -J63.
Close drain valves on heat exchanger and gas sampling probe.
Check pressure of cooling water in the controller and top up if
necessary (target cooling water pressure in cooled state: 1-1.5
Proceed as follows:
Check cooling water circuit for leaks. Remedy any leaks before
continuing with start-up.
up cooling water
for leaks