SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B 107
...Application 1
Device Setup / ...Application 8
Enter the name of the application 1
... 8.
Alphanumeric, max. 20 characters
...A1...Flow meas.’ ... ‘...A8...Flow meas.’ using .
...A1...Temp. meas.’ ... ‘...A8...Temp. meas.’ using .
...A1...Pipe type’ ... ‘...A8...Pipe type’ using .
...A1...Gas data’ ... ‘...A8...Gas data’ using .
...A1...Field Optim.’ ... ‘...A8...Field Optim.’ using .
Device Setup / ...Application 1 /
...A1...Flow meas.
Device Setup / ...Application 8 /
...A8...Flow meas.
Qm Max set the upper range value for the mass flow.
Set the lower range value for the mass flow.
Set the upper range value for standard volume flow.
Set the lower range value for standard volume flow.
Select the damping for fl
ow measurement.
The value set here relates to 1 τ (Tau). The value refers to the response time for a step flowrate change. It affects the
instantaneous value in the display and at the current output.
Default setting: 0.2 seconds
the switching threshold (0 to 10 %) for the low flow cut-off.
If the flow rate is below the switching threshold, there is no flow measurement. The setting of 0 % deactivates the low flow
cut
-off.
%
s (0 to 50 %) for the low flow cut-off as it is defined in the parameter ‘Low Flow Cut Off’.