EasyManua.ls Logo

ABB SensyMaster FMT430 - Cable Specification; PROFIBUS DP Communication

ABB SensyMaster FMT430
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70 SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
7 Electrical connections
Digital communication
1
Modbus master
2
Terminating resistor
3
Modbus slave 1
4
Modbus slave n to 32
Figure 63: Communication with the Modbus protocol
Cable specification
The maximum permissible length is dependent on the baud rate,
the cable (diameter, capacity and surge impedance), the number
of loads in the device chain, and the network configuration
(2-core or 4-core).
At a baud rate of 9600 and with a conductor cross-section of
at least 0.14 mm
2
(AWG 26), the maximum length is 1000 m
(3280 ft).
When using a 4-core cable as a 2-wire wiring system, the
maximum length must be halved.
The spur lines must be short, a maximum of 20 m (66 ft).
When using a distributor with ‘n’ connections, each branch
must have a maximum length of 40 m (131 ft) divided by ‘n.’
The maximum cable length depends on the type of cable used.
The following standard values apply:
Up to 6 m (20 ft):
cable with standard shielding or twisted-pair cable.
Up to 300 m (984 ft):
double twisted-pair cable with overall foil shielding and
integrated earth cable.
Up to 1200 m (3937 ft):
double twisted-pair cable with individual foil shielding and
integrated earth cables. Example: Belden 9729 or equivalent
cable.
A category 5 cable can be used for Modbus RS485 up to a
maximum length of 600 m (1968 ft). For the symmetrical pairs in
RS485 systems, a surge impedance of more than 100 Ω is
preferred, especially at a baud rate of 19200 and above.
PROFIBUS DP® communication
Note
The PROFIBUS DP® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
these protocols are suitable before implementation.
PROFIBUS DP interface
Terminals
V1
/ V2
Configuration
Via the PROFIBUS
DP interface or via the local
operating interface in connection with Asset Vision
Basic (DAT200) and a
corresponding Device Type
Manager (DTM)
Transmission
In accordance with IEC
61158-2
Baud rate
9.6 kbps, 19.2 kbps, 45.45 kbps, 93.75 kbps, 187.5
kbps, 500 kbps, 1.5 Mbps
The baud rate is automatically detected and does not
need to be configured manually
Device profile
PA Profile 3.02
Bus address
Address range 0
to 126
Factory setting: 126
Only one of the three different GSD files provided by ABB is
needed for commissioning.
Parameterization of the device can be performed via the display,
or through a device driver in the form of an EDD (Electronic
Device Description) or DTM (Device Type Manager).
You can download EDD, DTM and GSD from www.abb.com/flow.
The files required for operation can also be downloaded from
www.profibus.com.
ABB provides three different GSD files which can be integrated in
the system.
ID number
GSD file name
0x9740
PA139740.gsd
1
xAI, 1xTOT
0x3435
ABB_3435.gsd
6xAI, 2xTOT, 1xDI, 2xDO
0x9700
PA139700.gsd
1xAI
Users decide at system integration whether to install the full
range of functions or only part. Switching is made using the
Ident Nr. Selector’ parameter.
Refer to Ident Nr. Selector on page 121.

Table of Contents

Related product manuals