Installation and Commissioning Guide
Split Tri-Capacity
13
Installation and Commissioning Guide 500-700 Tri-Capacity Split Ducted
Doc. No.0525-098 Ver. 2 210330
07.02. CAY620T - CAY700T Unit Dimension
Unit Model
Number
Unit
Weight
Corner Weights(kg)
Centre Of
Gravity Position
A B C D E F XX YY
CAY620T 577 68 65 121 93 93 137 931 569
CAY700T 604 71 68 126 98 98 143 931 569
150
40
75
128
1695
O/A
30
50
30
97
(MTG C-C DIST 1115)(MTG C-C DIST 1115)
175
1470
XX
YY
2305 O/A
460
665
665
400
350
1195
O/A
ALL 50
LARGE LIQ
Ø 15.9 (5/8")
SMALL GAS
Ø 25.4 (1")
SMALL LIQ
Ø 12.7 (1/2")
30
30
(MTG C-C DIST 1135)
DETAIL P
6 x Ø 20.0
MTG. HOLES
4 x 25.4 (1")
LIFTING
POINT
CONDENSATE
DRAIN
25.4 (1")
BSP SOCKET
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
LARGE GAS
Ø 28.6 (1-1/8")
TOP VIEW
OVERALL NOMINAL DIMENSION H X W X D
= 1695 X 2305 X 1195
THIRD ANGLE
PROJECTION
SIDE VIEW
FRONT VIEW
NOTES:
1. Do not scale drawing. All dimensions are in mm unless specified. Refer to
corresponding unit dimensional drawing for mounting hole details.
2. Service Access Areas and Spaces for Airflow Clearances given are
suggested minimum based on the condition that the spaces around the
units are free from any obstructions and a walkway passage of 1000mm
between the units or between the unit and the outside perimeter is
available.
3. Minimum service access areas and spaces for airflow clearances are
responsibilities of the installer, ActronAir will not be held liable for any
extra charges incurred due to lack of access and space for airflow.
4. Under all circumstances, condenser air must not recirculate back onto
condenser coil. Keep all clearance free of any obstructions.
5. Maximum External Static of Outdoor Fans is 20 Pa.
6. STACKING OF UNITS: Ensure that minimum airflow and clearances are met.
7. Refer to Pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9. Use M12 bolt for feet mounting.
HEIGHT CLEARANCE = 1500
TOP VIEW
D
B
C
A
F
OUTDOOR COIL
OUTDOOR COIL
OUTDOOR COIL
SERVICE ACCESS AREAS
1000 mm
SERVICE
CLEARANCE
(COMPRESSOR
and
ELECTRICALS)
YY
XX
500 mm
AIRFLOW ALLOWANCE
500 mm
AIRFLOW ALLOWANCE
300 mm
SPACE CLEARANCE
E
DETAIL P