4.2.1.3.1.6.3 IntelligentOutputModules
Notification Appliance Circuit (NAC) Module - 55000-825ADV
The 55000-825ADV Notification Appliance Circuit (NAC) Module is an addressable module for use with the AX-CTL-
1L, AX-CTL-2 or AX-CTL-4 AX-CTL base card. Each module incorporates an independent, individually
programmable, notification appliance circuit (NAC), providing cost-effective solutions in areas requiring multiple
notification appliance circuits. Each 55000-825ADV allows switching of an external power supply, such as a 24 VDC
regulated power source or audio amplifier to a group of notification appliances.
The 55000-825ADV notification appliance circuit can be wired either Class A or B. Each module also supervises the
wiring for opens, shorts and grounds and reports this status back to the intelligent fire alarm control panel. Typical
input power to the 55000-825ADV would be from the main fire alarm control panel, a power supply booster or an
amplifier.
To increase the already rapid response activation of the 55000-825ADV, each module can be set to a group address,
allowing all 55000-825ADV’s assigned to a common group address to be activated from a single command poll from
the intelligent fire alarm control panel.
An eight position programming DIP switch is provided on each 55000-825ADV module for NAC Module addressing
and wiring classification definition. In additional, a four position programming DIP switch is provided for group
addressing (see figure 14 and 15).
The 55000-825ADV mounts to the front of a standard 4” square or 2-gang electrical outlet box. Displayed on the front
of each 55000-825ADV is a single red status LED which flashes when the device is polled.
Compatible with the Axis
AX
Dynamix I/O Relationship Programming, the 55000-825ADV module can be individually
assigned to activate from any input zone or address. In addition, the 55000-825ADV can be programmed to various
output relationships, timing functions, gated functions, etc. to perform project specific control operations.
E
O
L
L1L2
+
-
+
-
To N ex t
Peripheral
From
SLC Loop
Class B Wiring
47K
1/2 Watt
Programming
DIP Switches
A/B+
A/B-
A+A-
12345678
1
2
4
8
16
32
64
NO
B
S1
A
10
1234
1
2
4
8
NO
10
S2
TB2
TB3
TB1
Class A Wiring
A/B+
A/B-
A+A-
SOUNDER
PA
Vext- Vext+
+
-
-
+
24 VDC In
(NonResettable Power)
24 VDC Out
(NonResettable Power)
H H
H H
24VDC @ 1Amp Max
* Set Jumper
to Sounder
J1
Figure 14 - 55000-825ADV Notification Appliance Circuit Wiring