EasyManuals Logo

Allen-Bradley SmartGuard 600 User Manual

Allen-Bradley SmartGuard 600
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #185 background imageLoading...
Page #185 background image
Publication 1752-UM001A-EN-P - October 2006
Function Blocks Command Reference 185
3. As the workpiece continues to advance, the Output Enable
signal is kept on even if the light curtain is obstructed.
4. As the workpiece continues to advance, the light from sensor 11
is no longer interrupted by the workpiece, the muting status is
cleared, and the muting signal turns off.
Distance Settings
When setting up this type of muting application, the distance settings
must prevent a passing person from enabling the muting function, and
the light curtain and muting sensors must be set up so that a
workpiece passes by all of the muting sensors before the next
workpiece arrives at the muting sensors.
To calculate the appropriate setup distances for this example use
these formulas, where:
D1 = minimum distance required for muting sensor performance
d1 = maximum distance required for muting sensor performance
L = length of the workpiece
V = transit speed of the workpiece
T1min = controller cycle time
T1max= synchronization time setting (the default setting is 3
seconds)
Formula 1: D1 < L
Formula 2: V x T1min < d1 < V x T1max
For the muting function to operate effectively, both formulas must be
satisfied.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley SmartGuard 600 and is the answer not in the manual?

Allen-Bradley SmartGuard 600 Specifications

General IconGeneral
BrandAllen-Bradley
ModelSmartGuard 600
CategoryController
LanguageEnglish

Related product manuals