Sequoia Series 155
The power source can be programmed to turn off its output if the actual output voltage does not agree
within a given tolerance with the set value using the measurement query command.
Maximum Voltage
The maximum rms output voltage that can be programmed can be queried with:
VOLTage? MAX
The maximum voltage that the power source can output is limited by the maximum peak voltage
capability of the power source. This value is expressed in the equivalent rms value of a sinewave (crest
factor = 1.414). The maximum rms value is defined by the LIMIT subsystem. If a custom waveform is
selected with a crest factor higher than 1.414, the maximum rms voltage will be less than the LIMIT
value.