EasyManuals Logo

Ansul R-102 Installation And Maintenance Manual

Ansul R-102
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
SECTION 9 – APPENDIX
UL EX3470 ULC EX3470
PAGE 9-2 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
SYSTEM SELECTION GUIDE (Continued)
Total Tank Type of Carbon Dioxide Nitrogen
Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required
45-49 5 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429)
(Optional) 3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
50-55 5 Multiple 3 Gal. Reg. Release 101-30 (423443) Double (423493)
3 Gal. Additional Tank
3 Reg. Actuator N/A LT-A-101-30 (423491)
Double 3 Gal. Tank Box
50-55 5 Multiple 3 Gal. Reg. Release 101-20 (423441) LT-30-R (423435)
(Optional) 3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
56-60 6 Multiple 1.5 Gal. Reg. Release 101-30 (423443) Double (423493)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
61-66 6 Multiple 3 Gal. Reg. Release 101-30 (423443)** Double (423493)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
67-71 7 Multiple 1.5 Gal. Reg. Release 101-10 (423439) LT-20-R (423429)
(2) 3 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491)
(2) Double 3 Gal. Tank Box
67-71 7 Multiple Remote Mechanical Release 101-10 (423439) – –
(Optional) 3 Gal. Reg. Actuator 101-30 (423443) LT-A-101-30 (423491)
1.5 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-20 (423441)*** LT-30-R (423435)
72-77 7 Multiple 3 Gal. Reg. Release 101-20 (423441) LT-30-R (423435)
(2) 3 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491)
(2) Double 3 Gal. Tank Box
72-77 7 Multiple Remote Mechanical Release 101-10 (423439) – –
(Optional) 3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435)
* Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3 gal. system.
** If tanks are manifolded, only a “double tank” nitrogen cartridge (Part No. 423493) can be used.
*** If tanks are manifolded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used.

Table of Contents

Other manuals for Ansul R-102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul R-102 and is the answer not in the manual?

Ansul R-102 Specifications

General IconGeneral
AgentAnsulex Low pH Liquid Fire Suppressant
ActivationAutomatic or manual
Temperature Range32 °F to 120 °F (0 °C to 49 °C)
System TypeWet Chemical
ApplicationCommercial Kitchens
Nozzle CoverageVaries based on hazard and configuration
DetectionThermal or Manual
ApprovalUL 300
Nozzle TypesAppliance specific nozzles
CapacityVaries by cylinder size
MaterialStainless Steel
StandardsNFPA 17A
Cylinder Sizes1.5 to 3 gallons