SECTION 9 – APPENDIX
UL EX3470 ULC EX3470
PAGE 9-4 REV. 11 2014-SEP-01
R-102 Restaurant Fire Suppression Manual
SYSTEM SELECTION GUIDE (Continued)
Total Tank Type of Carbon Dioxide Nitrogen
Flow No.* Quantity System Type of Hardware Cartridge Required Cartridge Required
100-110 10 Multiple Remote Mech. Release 101-10 (423439) N/A
(3) 3 Gal. Reg. Actuator N/A (3) LT-A-101-30 (423491)
(3) Double 3 Gal. Tank Box
3 Gal. Reg. Actuator 101-20 (423441) LT-30-R (423435)
100-104 10 Multiple Remote Mechanical Release 101-10 (423439)
(Optional) 3 Gal. Reg. Actuator 101-30 (423443) LT-A-101-30 (423491)
1.5 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
100-104 10 Multiple Remote Mech. Release 101-10 (423439) N/A
(Optional) (2) 3 Gal. Reg. Actuator N/A (2) LT-A-101-30 (423491)
(2) Double 3 Gal. Tank Box
(2) 3 Gal. Reg. Actuator (2) 101-30 (423443) (2) LT-A-101-30 (423491)
3 Gal. Additional Tank
1.5 Gal. Additional Tank
105-110 10 Multiple Remote Mechanical Release 101-10 (423439) – –
(Optional) 3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
3 Gal. Reg. Actuator 101-30 (423443)*** LT-A-101-30 (423491)
3 Gal. Additional Tank
* Based on 5 flow numbers for a 1.5 gal. system and 11 flow numbers for a 3 gal. system.
** If tanks are manifolded, only a “double tank” nitrogen cartridge (Part No. 423493) can be used.
*** If tanks are manifolded, either an LT-A-101-30 nitrogen cartridge (Part No. 423491) or a double tank cartridge (Part No. 423493) can be used.
Options are available up to a maximum of 15 tanks. Contact Technical Services Department for detailed information.

Table of Contents

Other manuals for Ansul R-102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul R-102 and is the answer not in the manual?

Ansul R-102 Specifications

General IconGeneral
AgentAnsulex Low pH Liquid Fire Suppressant
ActivationAutomatic or manual
Temperature Range32 °F to 120 °F (0 °C to 49 °C)
System TypeWet Chemical
ApplicationCommercial Kitchens
Nozzle CoverageVaries based on hazard and configuration
DetectionThermal or Manual
ApprovalUL 300
Nozzle TypesAppliance specific nozzles
CapacityVaries by cylinder size
MaterialStainless Steel
StandardsNFPA 17A
Cylinder Sizes1.5 to 3 gallons