USE AND MAINTENANCE MANUAL
ATTILA
71
EN
PARAMETER 3/5T 15/20T UM DESCRIPTION
deC
yES yES flag
Decimal point enabling
▪ No = not active
▪ yES = active.
Ucf
C C flag Selection C = °C / F = °F.
ep1
yES yES flag
Probe enabling at core
▪ No = not active
▪ yES = active.
ep3
no no flag
Evaporator probe enabling
▪ No = not active
▪ yES = active.
fan
On On flag
Fan status in blasting
▪ CP = parallel to compressor
▪ On = always on.
fr1
CMP CMP flag
Digital output configuration R1
▪ OFF = Disabled
▪ rdO = Door resistance
▪ CF = Condenser fan
▪ HP = Core heating
▪ Uu = uv lamp
▪ Lig = Cell light
▪ dEF = Defrosting
▪ EF = Evaporator fan
▪ CMP = Compressor.
fr2
EF EF flag Digital output configuration R2. Similar to Fr1.
fr3
CF CF flag Digital output configuration R3. Similar to Fr1.
fr4
rdO rdO flag Digital output configuration R4. Similar to Fr1.
fr5
OFF C2F flag Digital output configuration R5. Similar to Fr1.
dbU
10 10 sec Buzzer sound duration.
ed0
yES yES flag
Door presence
▪ No = not active
▪ yES = active.
td0
30 30 sec Timer for door alarm signalling
enc
yES yES flag
Enabling negative blasting
▪ No = not active
▪ yES = active.