PARAMETER 3/5T 15/20T UM DESCRIPTION
sLd
Fan Fan flag
Stop utilities with open door
▪ CF = Stop compressor and fans
▪ Fan = Stop fans only.
UUT
5 5 C° Set sterilisation temperature.
prd
2 2 min Maximum Core heating duration.
prt
4 4 C° Set Core heating temperature.
s0C
34 34 min Set start temperature 2nd condenser fan.
s02
36 36 C° Set start temperature 3rd condenser fan.
sCf
60 60 C° High compressor block temperature set.
eps
3 3 n
Pressure switch setting
▪ 0=pressure switch disabled
▪ 1,2,3,4 = alarm events counting before locking loads.
pps
nC nC flag
Pressure switch polarity
▪ No = Normally open
▪ nC = Normally closed.
0fL
10 10 C°
Offset subtracted from set in storage for low temperature alarm
threshold.
Lae
yES yES flag
Minimum cell temperature alarm enabling
▪ No = not active
▪ yES = active.
0fH
10 10 C°
Offset subtracted from set in storage for high temperature
alarm threshold.
Hae
yES yES flag
Enabling maximum cell temperature alarm
▪ No = not active
▪ yES = active.
ps2
15 15 n Advanced parameter access password.