EasyManua.ls Logo

Baer DLX - 8 Interfaces; 8.1 General

Baer DLX
178 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
77
8 Interfaces
8.1 General
Three interfaces are available in the DLX unit:
Service interface for programming purposes and data retrieval
Data interface “Com1” for data retrieval on site (optional)
Modem interface “Com2” for remote data retrieval (optional); device can
also be equipped with a second data interface “Com2” instead of the mo-
dem.
8.1.1 Automatic protocol recognition
The DLX unit automatically recognizes the retrieval protocol (currently
SCTM, IEC60870-5-102 or the programming software DLXPARA). On both
direct interfaces (service interface and data interface/Com1) the first query
telegram will be lost in the case of a protocol change (the modem interface
can change the protocol without losing a telegram). Therefore DLXPARA
can be used to define the default protocol for the data interface (the default
protocol for the service interface is always the IE60870-5-102 protocol).
The DLX unit will switch to the default protocol after each programming ac-
tivity and after 5 minutes with no communication on the relevant interface.
Starting from version 1.05.00 it is possible to activate the protocol Modbus
RTU (instead of SCTM / IEC 60870-5-102 for the interfaces Com1 and
Com2 only).
Due to safety reasons the programming software can only communi-
cate with the service interface.
Remote parametering is not possible!

Table of Contents