11.7 Data storage on a PC-Card
The following information will always automatically be stored on a PC-Card
(independent from the program parameters of the unit):
Spontaneous events: the PC-Card will always contain at least the last 100
events.
Billing data: the PC-Card will always contain at least cumulative
rate less counter values of the last 4 reset instances.
By default (if nothing else was programmed with DLXPARA) the demand
values of counters 1 through to 16 for registration period Tm1 will be stored
for the last 35 days. The PC-Card will be used as a circular buffer, i.e. once
the buffer is full, the newest incoming value overwrites the oldest value.
You can use the programming software to activate storage of data for regis-
tration period Tm2. In addition, you can select which values shall be stored
and what the storage depth in days will be. For more information see page
36.
The PC-Card will only ever store values that have been registered or
calculated after the time when the card was insert and activated.