1640-IN-031-C-08
Page 24 of 104
Eurotherm/Barber-Colman
MACO Series Controller Installation
Figure 2.0 Installing Resistors for Current Inputs
A-60063-1XX or A-60133-1XX (12 Zones of Analog Input)
A-60063-2XX or A-60133-2XX (6 Zones of Analog Input)
Kit No. 71-975 consists of six 505 Ω, 1/2 W, 0.1%, 25 ppm resistors
2 Kits (12 Resistors)
1 Kit (6 Resistors)
T/C-Analog Assembly
Cut and form the resistors approximately as shown.
Insert one resistor lead with the plus (+) side of the input
and the other with the minus (-) side. Before applying
power, examine all leads for possible short circuits.
No. of Kits
Install these resistors ONLY on the assemblies shown above AND ONLY if the inputs
to the assembly are CURRENT (mAdc) instead of voltage.
T/C-Analog Card Specifications
Reference Accuracy: Common Mode Rejection:
0.25% of Span, ±1°C 135 dB @ 230 Vac 60Hz
Range: Series Mode Rejection:
Type J, 0 to 700°C (32 to 1292°F); 60 dB @ 150 mV 60 Hz
Type K, 0 to 950°C (32 to 1742°F)
0 to 10 Vdc
0 to 20 mAdc (scalable)
Control Zones:
A-60063-0XX A-60133-0XX 12 Zones of T/C Input
A-60063-1XX A-60133-1XX 12 Zones of Analog Input (Vdc or mAdc)
A-60063-2XX A-60133-2XX 6 Zones of T/C Input (Function B)
6 Zones of Analog Input (Vdc or mAdc)
A-60063-3XX A-60133-3XX 6 Zones of T/C Input (Function B)
A-60133-8XX 9 Zones T/C Input (Func A 1-6, Func B 1-3)
3 Zones Anlog In (Vdc, Func B 4-6)
Alarms:
2 Process High/ 1 Process Low
Deviation +/-
Heater Burnout (HBO, T/C inputs only)
Sensor Break
Control Modes:
Auto-Tuned PID (T/C Inputs only)
Manual Tune (T/C Inputs only)