142 9424200994 Rev N
Table 53. Operational Settings
Setting Range Increment
Unit of
Measure
Default
Mode
Disabled or Enabled
n/a
n/a
Disabled
Reverse Reach
0 to 500
varies
ohms
4
Forward Reach
0 to 500
varies
ohms
8.5
Blinder A Offset
0 to 500
varies
ohms
2.5
Blinder B Offset
0 to 500
varies
ohms
2.5
Blinder Angle
1 to 90
1
degrees
90
Blinder Traverse Time
Delay
0 to 10,000 varies milliseconds 100
Trip Delay
0 to 5,000
varies
milliseconds
100
Min I1 5 to 600 1
percent of CT
rating
5
I2/I1 Ratio
10 to 200
1
percent
10
Out of Step (78OOS) Protection BE1-11g