EasyManuals Logo

Basler BE1-11g User Manual

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #232 background imageLoading...
Page #232 background image
220 9424200994 Rev N
Setting Range Increment
Unit of
Measure
Default
Phase Current Threshold
0 or 0.5 to 16
0.01
amps
0
Neutral/Ground Current Threshold
0 or 0.5 to 16
0.01
amps
0
Negative-Sequence Current
Threshold
0 or 0.5 to 16 0.01 amps 0
Power
Demand values are continuously calculated for real power (A kW, B kW, C kW, Total kW), reactive power
(A var, B var, C var, Total var), and apparent power (A VA, B VA, C VA, Total VA).
Demand Power Reporting Settings
BESTCOMSPlus Navigation Path: Settings Explorer, Alarm Configuration, Demands
HMI Navigation Path: Settings Explorer, Alarm Configuration, Demands
Settings are made using BESTCOMSPlus. Use the Settings Explorer to open the Alarm Configuration,
Demands tree branch. Demand settings for real power thresholds include Forward Watt and Reverse
Watt. Demand settings for reactive power include Forward Var and Reverse Var. A setting for apparent
power threshold is also provided. The demand power interval is defined by the Phase Interval setting.
Enter the appropriate demand power reporting settings. Refer to Figure 154.
Table 85 summarizes the demand power reporting settings.
Table 85. Demand Power Reporting Settings
Setting
Range
Increment
Unit of Measure
Default
Forward Watt Threshold
0 or 1 to 8,500
varies
watts
0
Reverse Watt Threshold
0 or 1 to 8,500
varies
watts
0
Forward var Threshold
0 or 1 to 8,500
varies
vars
0
Reverse var Threshold
0 or 1 to 8,500
varies
vars
0
VA Threshold
0 or 1 to 8,500
varies
VA
0
Retrieving Demand Reporting Information
BESTCOMSPlus Navigation Path: Metering Explorer, Demand
HMI Navigation Path: Metering Explorer, Demand Meter
Values and timestamps in the demand registers are reported in primary values. They can be read at the
front-panel display, through BESTCOMSPlus, and through the web page interface.
Peak demand values can be preset by pressing the Edit key and changing the value. Write access to the
Reports functional area is required to preset values at the front panel.
To access demand data through BESTCOMSPlus, use the Metering Explorer to open the Demand tree
branch and select Demand Current (Figure 155), Demand Power (Figure 156), Demand Reactive Power,
or Demand Apparent Power. The Demand Reactive Power and Demand Apparent Power screens are
similar.
Demands BE1-11g

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11g and is the answer not in the manual?

Basler BE1-11g Specifications

General IconGeneral
BrandBasler
ModelBE1-11g
CategoryRelays
LanguageEnglish

Related product manuals