404 9424200994 Rev N
Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 153. Record the
results.
Step 6: (Optional.) Repeat steps 1 through 5 for Settings group 1, 2, and 3.
Step 7: (Optional.) Repeat steps 1 through 6 for 27X-2, 27X-3, and 27X-4.
Functional Test Report
Pickup Verification (3V0 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (3V0 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Pickup Verification (V1 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Step
Low
Actual
Pickup
High
Low*
Actual
Reset
High*
Pass/Fail
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Auxiliary Undervoltage (27X) Test BE1-11g