9424200994 Rev N 405
Timing Verification (V1 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Pickup Verification (V2 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Step
Low
Actual
Pickup
High
Low*
Actual
Reset
High*
Pass/Fail
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (V2 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Pickup Verification (Vx Fundamental Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.