9424200994 Rev N 405
Timing Verification (V1 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (V2 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Step
Pickup
Setting
Low
Actual
Pickup
High
Low*
Actual
Reset
High*
Pass/Fail
V1
VA
V1
VA
V1
VA
V1
VA
V1
VA
6
78.0
234.0
76.4
229.2
79.5
238.5
78.7
236.1
80.3
240.9
P / F
7
38.0
114.0
37.0
111.0
39.0
117.0
38.3
114.9
39.1
117.3
P / F
7
22.0
66.0
21.0
63.0
23.0
69.0
22.2
66.6
22.6
67.8
P / F
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (V2 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (Vx Fundamental Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Reset/Pickup Ratio = 102% ±1%
Step
Pickup Setting
Low
Actual Pickup
High
Low*
Actual Reset
High*
Pass/Fail
6
115.0 V
112.7 V
117.3 V
116.1 V
118.4 V
P / F
7
65.0 V
63.7 V
66.3 V
65.6 V
66.9 V
P / F
7
20.0 V
19.0 V
21.0 V
20.2 V
20.6 V
P / F
* Reset range is calculated from the pickup setting and may need adjusted based on actual pickup.