EasyManua.ls Logo

Basler BE1-11g - Functional Test Report

Basler BE1-11g
672 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
388 9424200994 Rev N
Table 135. Inverse Time and Definite Time Pickup Test Settings (25)
Setting
Value
Description
Voltage Difference
10%
Sets voltage difference to 10 V (10% of nominal, nominal = 100 V).
Nominal settings are defined on the System Parameters, Power
System screen in BESTCOMSPlus.
Slip Angle
10°
Sets slip angle to 10 degrees
Slip Frequency
0.3 Hz
Sets slip frequency to 0.3 Hz
Step 2: Prepare to monitor the 25 function operation. Operation can be verified by monitoring OUT1.
Step 3: As in the previous test, connect BE1-11g terminals C13 (A-phase), C14 (B-phase), and C15 (C-
phase) together. Apply a 120 Vac, 50 or 60 hertz ac, 0 degree voltage source (Line VTP) to the
three jumpered terminals and the neutral terminal (C16).
Step 4: Apply a second 120 Vac, 50 or 60-hertz ac, 0 degree voltage source (Auxiliary VTX) to C17 and
C18. OUT1 should close verifying the 25 output for a Slip Angle of 0 degrees, 0 Voltage
Difference, and 0 Slip Frequency.
Step 5: Decrease the Auxiliary voltage input (VTX) until OUT1 opens. Slowly increase the voltage until
OUT1 closes. Record the result.
Step 6: Repeat step 5 for the Line voltage input (VTP). Return voltage inputs to 120 Vac, 50 or 60-hertz,
0 degrees. Record the result.
Step 7: Swing the angle between voltage source 1 and 2 until the OUT1 opens. Slowly decrease the
angle until OUT1 closes. Pickup should occur on the leading and lagging side of 0 degrees.
Dropout should occur on the leading and lagging side of 0 degrees. Record the results.
Step 8: With the Auxiliary Voltage set at nominal frequency, step change the frequency of the Line
voltage input by 0.25 hertz (59.75 on a 60-hertz BE1-11g). Note that OUT1 is closing and
opening based on a slip rate of 0.25 hertz. Decrease the frequency until OUT1 stays open.
Record the result. Also, check on the fast side (60.25 for a 60-hertz BE1-11g). Record the
result.
Step 9: Repeat step 8 for the Auxiliary Voltage input. Record the results.
Step 10: (Optional.) Repeat steps 3 through 9 for settings group 1, 2, and 3.
Functional Test Report
VTP and VTX Live Voltage, Dead Voltage Pickup Test (25 Voltage Monitor)
Accuracy = ±2%
Step
Setting
Low
Actual
High
Pass/Fail
6
VTP - Dead V Dropout - 55.0 V
53.9 V
56.1 V
P / F
7
VTP - Live V Pickup - 90.0 V
89.2 V
91.8 V
P / F
9
VTX - Dead V Dropout - 55.0 V
53.9 V
56.1 V
P / F
10
VTX - Live V Pickup - 90.0 V
89.2 V
91.8 V
P / F
Live/Dead Dropout Timing Verification (25 Voltage Monitor)
Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Dropout Delay Setting
Low
Actual Timing
High
Pass/Fail
4
VTP - Dead V Dropout Delay - 50 ms
18 ms
82 ms
P / F
5
VTP - Live V Dropout Delay - 50 ms
18 ms
82 ms
P / F
6
VTP - Dead V Dropout Delay - 2000 ms
1,968 ms
2,032 ms
P / F
6
VTP - Live V Dropout Delay - 2000 ms
1,968 ms
2,032 ms
P / F
Sync-Check (25) Test BE1-11g

Table of Contents

Related product manuals