EasyManuals Logo

Basler BE1-11g User Manual

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #644 background imageLoading...
Page #644 background image
632 9424200994 Rev N
Figure 386. Module 1 Output #1 Screen
Table 258 summarizes the configuration settings for remote analog outputs.
Table 258. Configuration Settings for Remote Analog Outputs
Setting
Range
Increment
Unit of Measure
Default
Param Selection
Voltages, Currents, Frequency,
Power, etc.
n/a n/a VA
Output Type
Voltage or Current
n/a
n/a
Voltage
Param Min
99,999.9 to 99,999.9
0.1
n/a
99,999.9
Param Max
99,999.9 to 99,999.9
0.1
n/a
99,999.9
Min Input Current
4 to 20
0.01
milliamps
4
Max Input Current
4 to 20
0.01
milliamps
20
Min Input Voltage
0 to 10
0.01
volts
0
Max Input Voltage
0 to 10
0.01
volts
10
Remote Analog Output Metering
Analog output metering values are obtained through BESTCOMSPlus by using the Metering Explorer to
open the Analog Metering, Analog Outputs tree branch. BESTCOMSPlus must be online with the BE1-
11g to view analog output metering. Alternately, values can be obtained through the front-panel display by
navigating to Metering > Analog Metering > Analog Output.
Remote RTDs Configuration
The RTD module provides 12 RTD inputs. The BE1-11g supports two RTD modules at once. The RTDs
are always monitored and their status is displayed on the appropriate metering screens. The BE1-11g
reports Out of Range when an RTD module is disconnected.
Protection settings for remote RTDs are described in the Resistance Temperature Detector (49RTD)
Protection chapter.
Configuration Settings
BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Remote RTD
HMI Navigation Path: Settings Explorer, RTD Types
Configuration settings are made using the BE1-11 plugin for BESTCOMSPlus. Before making
configuration settings, remote module communications must be configured on the System Parameters,
Remote Module Communications screen. To program the configuration settings, use the Settings
Explorer to open the Programmable Outputs, Remote RTD, RTD Type Selection tree branch and select
RTD Type Selection. Use the drop-down menu to select RTD Type. Refer to Figure 387.
RTD Module BE1-11g

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11g and is the answer not in the manual?

Basler BE1-11g Specifications

General IconGeneral
BrandBasler
ModelBE1-11g
CategoryRelays
LanguageEnglish

Related product manuals