9424200994 Rev N 345
CBA3
VarsVarsVarsVars ++=
φ
where:
For Sensing Type: Three-wire
In three-wire sensing mode, the equivalent LN voltages are determined from the LL voltages assuming
3V
0
= 0V. This allows per-phase watts and vars to be determined and provides improved accuracy over a
two-element method when neutral current is present.
Using the computed PN voltages, watts and vars are then computed using the equations listed under
four-wire sensing type, above.
For Single Phase Sensing Types: AN, BN, CN, AB, BC, CA
In single-phase sensing mode, the unknown PN voltages are calculated. Assuming a balanced three-
phase voltage is applied, the unknown PN voltages can be determined by scaling and rotating the
measured voltage as follows:
ABC Rotation
AN Sensing:
BN Sensing:
CN Sensing:
AB Sensing:
BC Sensing:
CA Sensing:
ACB Rotation
AN Sensing:
BN Sensing:
CN Sensing:
AB Sensing:
BC Sensing:
CA Sensing:
Using both the measured and calculated PN voltages, watts and vars are then computed using the
equations listed under four-wire sensing type above.
BE1-11g Configuration