384 9424200994 Rev N
Step
Pickup
Setting
Low
Actual
Pickup
High
Low*
Actual
Dropout
High*
Pass/Fail
15
2.36
2.31 V/Hz
2.41 V/Hz
2.289 V/Hz
2.336 V/Hz
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Inverse Time Verification
Time Dial Range = 0.0 to 9.9
Timing Accuracy = ±5% or ±50 ms, whichever is greater
Step
Time
Dial
Setting
Percent of
Nominal V/Hz
Step Voltage Low Actual Timing High Pass/Fail
3
0.5
110%
132 V
47.5 sec
52.5 sec
P / F
3
0.5
120%
144 V
11.875 sec
13.125 sec
P / F
3
0.5
140%
168 V
2.945 sec
3.255 sec
P / F
4
1.0
110%
132 V
95 sec
105 sec
P / F
4
1.0
120%
144 V
23.75 sec
26.25 sec
P / F
4
1.0
140%
168 V
5.985 sec
6.615 sec
P / F
4
2.0
110%
132 V
190 sec
210 sec
P / F
4
2.0
120%
144 V
47.5 sec
52.5 sec
P / F
4
2.0
140%
168 V
11.875 sec
13.125 sec
P / F
Inverse Time Reset Verification
Time Dial Range = 0.0 to 9.9
Timing Accuracy = ±5% or ±50 ms, whichever is greater
Step
Time Dial Setting
Low
Actual Timing
High
Pass/Fail
3
0.5
5.937 sec
6.562 sec
P / F
4
1.0
11.875 sec
13.125 sec
P / F
4
2.0
23.75 sec
26.25 sec
P / F
Definite Time Verification
Time Dial Range = 0 to 600,000
Timing Accuracy = ±0.5% or ±50 ms, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
3
500 ms
450 ms
550 ms
P / F
4
1,000 ms
950 ms
1,050 ms
P / F
4
5,000 ms
4,950 ms
5,050 ms
P / F
Overexcitation (24) Test BE1-11g