9424200994 Rev N 421
Pickup Verification (Vx Fundamental Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98% ±1%
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (Vx Fundamental Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Pickup Verification (Vx Third Harmonic Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98% ±1%
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (Vx Third Harmonic Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
BE1-11g Auxiliary Overvoltage (59X) Test