444 9424200994 Rev N
Dropout should occur between 93-99% of the actual pickup value.
Step
Pickup Setting
Low
Actual
Pickup
High
Low*
Actual
Dropout
High*
Pass/Fail
I2
IA
I2
IA
I2
IA
I2
IA
I2
IA
6
0.5
(5A CT)
1.5 0.42 1.26 0.57 1.71 0.46 1.38 0.49 1.47 P / F
7
5.0
(5A CT)
15.0 4.85 14.55 5.15 15.45 4.65 13.95 4.95 14.85 P / F
7
9.0
(5A CT)
27.0 8.73 26.19 9.27 27.81 8.37 25.11 8.91 26.73 P / F
6
0.1
(1A CT)
0.3 0.08 0.24 0.11 0.33 0.093 0.279 0.099 0.297 P / F
7
1.0
(1A CT)
3.0 0.97 2.91 1.03 3.09 0.93 2.79 0.99 2.97 P / F
7
1.8
(1A CT)
5.4 1.74 5.22 1.85 5.55 1.67 5.01 1.78 5.34 P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (I2 Mode)
Time Delay Range = 0 to 60,000 ms
Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,942 ms
2,058 ms
P / F
5
5,000 ms
4,927 ms
5,073 ms
P / F
5
10,000 ms
9,902 ms
10,098 ms
P / F
Pickup Verification (IG Mode)
Pickup Setting Range = 0.5 to 150 A for 5A sensing
0.1 to 30 A for 1A sensing
0.01 to 7.5 for SEF
Pickup Accuracy = ±2% or ±50 mA, whichever is greater for 5A sensing
±2% or ±10 mA, whichever is greater for 1A sensing
±2.5% or ±2.5 mA, whichever is greater for SEF
Dropout should occur between 93-99% of the actual pickup value.
Step
Pickup Setting
Low
Actual Pickup
High
Low*
Actual Dropout
High*
Pass/Fail
6
0.5 A (5A CT)
0.45 A
0.55 A
0.465 A
0.495 A
P / F
7
5.0 A (5A CT)
4.9 A
5.1 A
4.65 A
4.95 A
P / F
7
20.0 A (5A CT)
20.6 A
20.4 A
18.6 A
19.8 A
P / F
6
0.1 A (1A CT)
0.09 A
0.11 A
0.093 A
0.099 A
P / F
7
1.0 A (1A CT)
0.98 A
1.02 A
0.93 A
0.99 A
P / F
7
2.0 A (1A CT)
1.96 A
2.04 A
1.86 A
1.98 A
P / F
6
0.1 A (SEF)
0.09 A
0.11 A
0.093 A
0.099 A
P / F
7
1.0 A (SEF)
0.85 A
1.15 A
0.93 A
0.99 A
P / F
7
2.0 A (SEF)
1.95 A
2.05 A
1.86 A
1.98 A
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Instantaneous Overcurrent (50) Test BE1-11g

Table of Contents

Related product manuals