EasyManuals Logo

Basler BE1-11g User Manual

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #518 background imageLoading...
Page #518 background image
506 9424200994 Rev N
Setting
Value
BESTCOMSPlus Screen
Description
Phase VT Ratio
1
System Parameters, Sensing
Transformers
Sets phase VT ratio to
1
Phase VT
Connection
4W-Y
System Parameters, Sensing
Transformers
Sets phase VT
connection to 4W-Y
27/59 Mode
PN
System Parameters, Sensing
Transformers
Sets 27/59 mode to
phase-neutral
Block Impedance
Elements
Disabled
(unchecked)
Alarm Configuration, Fuse Loss
(60FL)
Disables fuse loss
protection
Element Mode
Both
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Enables both the non
voltage control and
voltage control
elements
Directional
Supervision Angle
45.0
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the supervisory
angle to 45°
mho Characteristic 1
Diameter
(secondary ohm)
10.0
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the first mho
characteristic diameter
to 10.0
mho Characteristic 1
Offset
(secondary ohm)
5.0
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the first mho
characteristic offset to
5.0
mho Characteristic 1
Time Delay (ms)
2,000
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the non voltage
control 40Z time delay
to 1,000 ms
mho Characteristic 1
Voltage Pickup
(secondary V)
8
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the supervisory
voltage inhibit to 10V
mho Characteristic 1
Voltage Time Delay
(ms)
1,000
Protection, Impedance, Loss of
Excitation Impedance Based (40Z)
Sets the voltage
controlled 40Z time
delay to 2,000 ms
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 313.
Blocking is disabled.
OUT1 closes for non-voltage control trip.
OUT2 closes for non-voltage control pickup
OUT3 closes for voltage control trip.
OUT4 closes for voltage control pickup.
Fault recording is enabled.
Step 3: Prepare to monitor the 40Z function operation. Operation can be verified by monitoring OUT2
(40Z pickup) and OUT4 (40Z VC pickup, see Figure 313).
Step 4: Connect and apply balanced three-phase 2.090° A, 2.0330° A, 2.0210° A to terminals D1
through D6 and a balanced three-phase 11.00° V, 11.0240° V, 11.0120° V phase-neutral
voltage source to terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (Neutral).
All outputs should remain open.
Step 5: Slowly decrease the voltage level until OUT2 closes. Record the pickup. This should occur at
10V ±0.3 V. Verify that there is a 40Z-Z1 target on the front-panel display.
Step 6: Continue decreasing the voltage until OUT4 closes (VC pickup). Record the pickup. This should
occur at 8V ±0.08V. Slowly increase voltage until OUT4 opens. Continue increasing until OUT2
Loss of Excitation Impedance Based (40Z) Test BE1-11g

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11g and is the answer not in the manual?

Basler BE1-11g Specifications

General IconGeneral
BrandBasler
ModelBE1-11g
CategoryRelays
LanguageEnglish

Related product manuals